Energy meter M2DL2

M2DL2 Energy meter and nework analyzer

 

The M2DL2 energy meter and network analyzer is designed to act as an energy meter and also measures parameters of a single phase network, such as voltage, current, active power, reactive power factor and frequency in low voltage.

    
The M2DL2 is characterized through its RS-485 communication with potential to connect up to 32 computers in a same loop or 128 through converter, being able to be controlled from any computer or any other network device.

MODELORDERING CODE
M2DL2YM2DL23303
 fo m2dl2 l

 tira-m2dl2-01eng

GENERAL FEATURES 

• Single-phase 

• Accuracy Cl.1 active Cl.2 reactive (EN 62053)

• Direct measurement up to 80 A

• RS-485 communication. MOD BUS protocol

• Energy consumption LED

• LCD display 6 digits

• Pulse output: SO (DIN 43864)

• 2 DIN modules

• Partial active energy counter resettable

 ELECTRICAL PARAMETERUNIT
 Voltage V
 Current A
Active power (P) kW
Reactive power (Q)kvar
Power factor (Cos φ)PF
FrequencyHz
Import active energy (EP+)kWh
Export reactive energy (EP-)kWh
Reactive energy (Q1, Q2, Q3, Q4)kvarh

VOLTAGE INPUT 

Rated voltage (Un)230  V  AC
Burden< 8 V A, 2 W
Operating range± 30 % U n
Frequency50 – 60 Hz

CURRENT INPUT

Current  IB  (IMAX)5  (80)  A
Burden<  1  VA
Operating range0-100 % IMAX
Starting current (In)< 0,4 % IB

GENERAL FEATURES

Counter typeDisplay  LCD
Digits5 enteros + 1 decimal
Active energy counterTotal and partial
Class1 active – 2 reactive
Dimensions2 modules (35 mm)

 

CATALOGUE M2DL2

PORTADA M2DL2 ENG

pdf CATALOGUE M2DL2


More new products   

Energy meters 

2 ENG

pdf Energy meters